16. Protection Features
*) In case of a protection event, audible noise may occur.
17. Safety Features
18. Dielectric Strength
The output voltage is floating and has no ohmic connection to the ground. Type and factory tests are conducted by the manufacturer. Field tests may be
conducted in the field using the appropriate test equipment which applies the voltage with a slow ramp (2s up and 2s down). Connect all input-
terminals together as well as all output poles before conducting the test. When testing, set the cut-off current settings to the value in the table below.
Output protection
Electronically protected against overload, no-load and short-circuits
*)
Output over-voltage protection typ. 30.5Vdc
max. 32Vdc
In case of an internal power supply defect, a redundant circuit limits the maximum
output voltage. The output shuts down and automatically attempts to restart.
Degree of protection IP 20 EN/IEC 60529
Penetration protection > 5mm e.g. screws, small parts
Over-temperature protection yes Output shut-down with automatic restart
Input transient protection MOV (Metal Oxide Varistor)
Internal input fuse included not user replaceable
Input / output separation
*)
SELV IEC/EN 60950-1
PELV IEC/EN 60204-1, EN 50178, IEC 62103, IEC 60364-4-41
double or reinforced insulation
Class of protection I PE (Protective Earth) connection required
Isolation resistance > 5MOhm input to output, 500Vdc
PE resistance < 0.1Ohm
Touch current (leakage current) typ. 0.14mA / 0.37mA 100Vac, 50Hz, TN-,TT-mains / IT-mains
typ. 0.20mA / 0.55mA 120Vac, 60Hz, TN-,TT-mains / IT-mains
typ. 0.35mA / 0.87mA 230Vac, 50Hz, TN-,TT-mains / IT-mains
max. 0.17mA / 0.46mA 110Vac, 50Hz, TN-,TT-mains / IT-mains
max. 0.26mA / 0.67mA 132Vac, 60Hz, TN-,TT-mains / IT-mains
max. 0.46mA / 1.08mA 264Vac, 50Hz, TN-,TT-mains / IT-mains
*) double or reinforced insulation
Fig. 18-1: Dielectric strength
ABC D
Type test 60s 2500Vac 3000Vac 1500Vac 500Vac
Factory test 5s 2500Vac 2500Vac 1000Vac 500Vac
Field test 5s 2000Vac 2000Vac 1000Vac 500Vac
Cut-off current setting > 15mA > 15mA > 20mA > 1mA
To fulfil the PELV requirements according to EN60204-1 § 6.4.1, we recommend that either the + pole,
the – pole or any other part of the output circuit shall be connected to the protective earth system. This
helps to avoid situations in which a load starts unexpectedly or can not be switched off when unnoticed
earth faults occur.
AD
C
B
B
N
L
Input DC-ok
Ear t h , PE
Output
-
+