User Manual

All parameters are specified at 24V, 2.1A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.
Rockwell Automation Publication 1606-RM034A-EN-P — March 2014 11
Bulletin 1606 Switched Mode Power Supplies
16. EMC
The CE mark indicates conformance with EMC guideline 89/336/EEC, 93/68/EEC and the low-voltage directive (LVD)
73/23/EWG.
EMC Immunity
EN 61000-6-2, EN 61000-6-1
Generic standards
Electrostatic discharge EN 61000-4-2 Contact discharge
Air discharge
8kV
8kV
Criterion A
Criterion A
Electromagnetic RF eld EN 61000-4-3 80MHz-1Ghz 10V/m Criterion A
Fast transients (Burst) EN 61000-4-4 Input lines 4kV Criterion A
Output lines
2kV Criterion A
Surge voltage on input EN 61000-4-5 L
N
N / L
PE
2kV
4kV
Criterion A
Criterion A
Surge voltage on output EN 61000-4-5 +
-
+ / -
PE
500V
500V
Criterion A
Criterion A
Conducted disturbance EN 61000-4-6 0,15-80MHz 10V Criterion A
Mains voltage dips EN 61000-4-11 0% of 100Vac
40% of 100Vac
70% of 100Vac
0% of 200Vac
40% of 200Vac
70% of 200Vac
0Vac, 20ms
40Vac, 200ms
70Vac, 500ms
0Vac, 20ms
80Vac, 200ms
140Vac, 500ms
Criterion A
Criterion C
Criterion A
Criterion A
Criterion A
Criterion A
C noiretirC sm0005 ,caV0 Voltage interruptions EN 61000-4-11
Input voltage swells Rockwell Automation internal standard
A noiretirC sm005 ,caV003
Powerful transients VDE 0160 over entire load
range
750V, 1.3ms Criterion A
Criteria:
A: Power supply shows normal operation behavior within the dened limits.
C: Temporary loss of function is possible. Power supply might shut-down and restarts by itself. The power supply will incur no
damage or hazard.
EMC Emission
sdradnats cireneG 4-6-00016 NE ,3-6-00016 NE
Conducted emission EN 55011, EN 55022, FCC Part 15, CISPR 11, CISPR 22 Class B, input lines
senil tuptuo ,B ssalC 22055 NE
B ssalC 22055 NE ,11055 NE noissime detaidaR
dellifluF 2-3-00016 NE tnerruc tupni cinomraH
Voltage uctuations, icker dellifluF 3-3-00016 NE
This device complies with FCC Part 15 rules.
Operation is subjected to the following two conditions: (1) this device may not cause harmful interference, and (2) THIS
device must accept any interference received, including interference that may cause undesirable operation.
Switching frequency
variable, typ. 100kHz, (60-275kHz) Input voltage and output load dependent