Reference Manual User guide
All parameters are specified at 48V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Rockwell Automation Publication 1606-RM045A-EN-P — March 2014 5
Bulletin 1606 Switched Mode Power Supplies
4. DC-Input
1606-XLS240F:
DC input nom. DC 110-150V -20%/+25%
DC input range min. 88-187Vdc continuous operation
DC input current typ. 2.37A 110Vdc, at 24V, 10A
1606-XLS240F-D:
DC input nom. DC 110-300V -20%/+25%
DC input range min. 88-375Vdc continuous operation
DC input current typ. 2.37/ 0.85A 110/300Vdc, at 24V, 10A
All units:
Allowed Voltage L/N to Earth max. 375Vdc continuous, IEC 62103
Turn-on voltage typ. 80Vdc steady state value
Shut-down voltage typ. 55Vdc steady state value
Fig. 4-1 Wiring for DC Input
Instructions for DC use:
+
-
Load
L
PE
+
-
Power Supply
AC
Battery
N
DC
a) Use a battery or similar DC source.
For other sources, please contact Rockwell Automation.
b) Connect +pole to L and –pole to N.
c) Connect the PE terminal to a earth wire or to the machine
ground.