User Manual, 2-6 Amp Owner manual
Rockwell Automation Publication 1608N-UM001B-EN-P - May 2014 11
Chapter 3
Specifications and Dimensions
Technical Specifications
Table 5 - Technical Specifications – MiniDySC (2...6 Amps)
Electrical Input/Output (Normal Mode—Static Switch)
Connection Configuration Series-connected with load. Under normal line condition, the static switch passes utility voltage directly to the load
Standard Input Voltage DySC 1Phase: 120, 208, 220, 230, 240V
Voltage Range ±10%
Current Overload
(Trip above these levels)
110% continuous, 150% @ 10 sec., 200% @ 0.5 sec., 300% @ 10 cycles, 400% @ 3 cycles, 1000% Instantaneous
Frequency 50/60 Hz Auto Sensing
Frequency RangeUSBDLJOH 45 t
o 65 Hz
Surge Protect
ion Device (SPD) Built-in 3-Layers consisting of MOVs & Capacitors
Efficiency 250 VA > 94%, 500 VA > 97%, 750 VA > 96%
Phase (wiring) 1 phase (L-L & L-N)
Detection Voltage 88.5% of rated voltage
Response Time (typical) 0.7 ms detection, 1.2 ms inverter reaction (<2ms)
Electrical Output (Sag Correction Mode—Inverter)
Output Voltage Matches pre-sag input voltage
Voltage Regulation ±5% typical, +5% / -13% of nominal max
Output Current Rated RMS (2A ... 6A) with 300% instantaneous peak max
Crest Factor (at rated load) 3.0
Load Power factor range -0.5 ...+0.9, DC component <2% of rated current
Voltage Waveform (typical) Sine wave
Voltage Sag Correction Times
Single Event
87% to 50% voltage remaining 5 seconds SR & ER
Sags to zero voltage remaining 50ms or 200ms (standard or extended run time DySCs). Based on nameplate ratings with a power factor of 0.7
Multiple Events
Max Sag Correction Time 5 seconds cumulative usage
Seqential Sag Recovery 0 seconds (assuming cumulative run-time available)
Full Recovery Time Max 5 minutes to full recovery
Mechanical
Enclosure Ratings NEMA 1 (IP20)
Cooling Forced air (500VA, 750VA) or natural convection (250VA)
Access Lower front for connections
Accessibility (Wiring) Pluggable compression terminal block
Communications / User Interface
Indicators 3 LEDs: Overload Trip, Normal, Alarm
Connectivity Form C contacts rated 120Vac@0.5A or 30Vdc@1A
Environmental
Ambient Temperature 0 ...+50°C
Storage Temperature -40°C ...+75°C
Relative Humidity 0 ...95% non-condensing
Altitude Rated current available to 1000m (3300ft)
Certifications
Agency Approvals cULus recognized, Exceeds SEMI F47 Standard