User Manual, 2-6 Amp Owner manual

Rockwell Automation Publication 1608N-UM001B-EN-P - May 2014 7
Chapter 2
Operation
Ground Connection
Connect the safety ground (earth) conductor to the #8-32 (4.2mm dia.)
ground stud (Refer to Figure 3 on page 8
or Figure 4 on page 8).
Torque to 20 lb-in (2.3 N-m)
Note: The MiniDySC must be safety grounded according to the National Electrical Code. All local, state, and
federal regulations applicable to the installation of electrical systems apply.
Power Connections
First remove the 6-pin terminal block connector by removing two retaining
screws and pulling out. After connections are made reinstall terminal block
connector by pressing back in place and tightening the two retaining screws.
Wire Size: 26 - 12 AWG (0.13 - 3.31 mm
2
)
Wire Strip Length: 0.256" (6.5 mm)
To r q u e : 5 l b -in (0.6 N-m)
Line Connections (Input)
For Line-Neutral MiniDySC (part numbers ending in V2S or V2E): connect
utility L1 (hot) and N (neutral) to terminals labeled L1 (pin 5) and N (pin
6) as shown in Figure 3 on page 8
.
For Line-to-Line MiniDySC (part numbers ending in V1S or V1E): connect
utility L1 and L2 to terminals labeled L1 (pin 5) and L2/X2 (pin 6) as
shown in Figure 4 on page 8
.
Load Connections (Output)
For Line-Neutral MiniDySC (part numbers ending in V2S or V2E): connect
load wires to terminals labeled X1 (pin 4) and N (pin 6) as shown in Figure 3
on page 8.
For Line-to-Line MiniDySC (part numbers ending in V1S or V1E): connect
load wires to terminals labeled X1 (pin 4) and L2/X2 (pin 6) as shown in
Figure 4 on page 8
.