Installation Instructions 1734 POINT I/O Dual Port EtherNet/IP Adapter Catalog number 1734-AENTR, Series B Table of Contents Topic Page Important User Information 2 Environment and Enclosure 3 Preventing Electrostatic Discharge 3 North American Hazardous Location Approval 5 European Hazardous Location Approval 6 About The Adapter 7 Before You Begin 8 Determine Compatibility 8 Understand Messaging 8 Configure Autobaud 8 Install the Adapter 9 Set the Network Address 11 Replace The A
1734 POINT I/O Dual Port EtherNet/IP Adapter Important User Information Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.rockwellautomation.
1734 POINT I/O Dual Port EtherNet/IP Adapter 3 Environment and Enclosure ATTENTION: This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating. This equipment is not intended for use in residential environments and may not provide adequate protection to radio communication services in such environments. This equipment is supplied as open-type equipment.
1734 POINT I/O Dual Port EtherNet/IP Adapter Additional Resources Refer to these related publications, as needed. Resource Description 1734 POINT I/O® and 1738 ArmorPOINT I/O® Dual Port EtherNet/IP Adapter User Manual, publication 1734-UM017. A detailed description of module functionality, configuration, installation procedure and information on how to use the POINT I/O and ArmorPOINT I/O Dual Port EtherNet/IP adapters (1734-AENTR, Series B and 1738-AENTR, Series B, respectively).
1734 POINT I/O Dual Port EtherNet/IP Adapter 5 North American Hazardous Location Approval The following information applies when operating this equipment in hazardous locations: Informations sur l’utilisation de cet équipement en environnements dangereux: Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only.
1734 POINT I/O Dual Port EtherNet/IP Adapter European Hazardous Location Approval The following applies when the product bears the Ex Marking This equipment is intended for use in potentially explosive atmospheres as defined by European Union Directive 94/9/EC and has been found to comply with the Essential Health and Safety Requirements relating to the design and construction of Category 3 equipment intended for use in Zone 2 potentially explosive atmospheres, given in Annex II to this Directive.
1734 POINT I/O Dual Port EtherNet/IP Adapter 7 About The Adapter Read this publication for information about the Series B, POINT I/O Dual Port EtherNet/IP adapter, a communications adapter for POINT I/O modules. This adapter is for the POINT I/O backplane that provides connectivity to an EtherNet/IP network with two RJ-45 connectors for 2 port pass-through to support daisy-chain or ring, and the existing star and tree network topologies.
1734 POINT I/O Dual Port EtherNet/IP Adapter Before You Begin To effectively use your adapter, note the following considerations. Determine Compatibility RSLogix 5000™ software version 17, or greater, must be used for the 1734-AENTR Add-on Profile. The 1734-AENTR adapters will accept I/O connections with electronic keying for the 1734-AENT. This allows the 1734-AENTR adapter to be used in a daisy-chain topology with the 1734-AENT profile used for the 1734-AENTR.
1734 POINT I/O Dual Port EtherNet/IP Adapter 9 Install the Adapter Follow this procedure to install the adapter on the DIN rail. ATTENTION: You must only use Series C POINT I/O modules with 1734-AENTR EtherNet/IP Adapters. Series A or Series B POINT I/O modules will not work with 1734-AENTR EtherNet/IP Adapters (does not apply to POINTGuard modules). Mount the POINT I/O Dual Port EtherNet/IP Adapter on a DIN Rail Position the I/O adapter vertically above the DIN rail.
1734 POINT I/O Dual Port EtherNet/IP Adapter 2. Press down firmly to install the adapter on a DIN rail, noting that the locking mechanism locks the adapter to the DIN rail. 3. Set the network address thumbwheel switches to the desired value. See Set the Network Address for more information on setting the IP address. 4. Slide the safety end cap up to remove it, exposing the backplane and power interconnections. ATTENTION: Do not discard the end cap.
1734 POINT I/O Dual Port EtherNet/IP Adapter 11 Set the Network Address The thumbwheel switches are set to 999 and DHCP enabled, by default. You can set the network Internet Protocol (IP) address in the following ways: • Use the thumbwheel switches on the adapter. • Use a Dynamic Host Configuration Protocol (DHCP) server, such as Rockwell Automation BootP/DHCP. • Retrieve the IP address from nonvolatile memory.
1734 POINT I/O Dual Port EtherNet/IP Adapter If you set the switches to an invalid number (for example, 000 or a value greater than 254 excluding 888), the adapter checks to see if you enabled DHCP. DHCP Enabled and Not Enabled DHCP State Adapter Action Enabled Asks for an address from a DHCP server. The DHCP server also assigns other Transport Control Protocol (TCP) parameters. Not enabled Uses the IP address (along with other TCP configurable parameters) stored in nonvolatile memory.
1734 POINT I/O Dual Port EtherNet/IP Adapter 13 WARNING: If you connect or disconnect the communications cable with power applied to this module or any device on the network, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. 3. Remove the adjacent module from its base. 4. Use a small bladed screwdriver to rotate the DIN rail locking screw to a vertical position.
1734 POINT I/O Dual Port EtherNet/IP Adapter Wire The Adapter 002 1734-AENTR Series B POINT I O Module Status Network Activity Network Status Point Bus Status Link 1 Activity/ Status System Power Ethernet RJ-45 connectors IP ADDRESS Field Power NC Chas Gnd Link 2 Activity/ Status C V NC = No Connection Chas GND = Chassis Ground C = Common V = Supply 0 1 NC NC Chas Gnd Chas Gnd 2 3 4 V DC 5 C C V V 6 7 44848 IMPORTANT Do not connect 120/240V AC power to this supply.
1734 POINT I/O Dual Port EtherNet/IP Adapter 15 WARNING: Do not wire more than two conductors on any single terminal. WARNING: To comply with the CE Low Voltage Directive (LVD), this equipment must be powered from a Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV) compliant source. WARNING: If you connect or disconnect wiring while the field-side power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations.
1734 POINT I/O Dual Port EtherNet/IP Adapter Interpret Status Indicators Refer to the following diagram and table for information on how to interpret the status indicators.
34 POINT I/O Dual Port EtherNet/IP Adapter 17 Indicator Status for Modules Network status Off Device is not on-line - Device has not completed dup_MAC_id test. - Device not powered - check module status indicator Flashing green Device is on-line but has no CIP connections in the established state. Solid green Device on-line and has CIP connections in the established state. Flashing red One or more CIP connections in timed-out state. Check for I/O module failure and controller operation.
1734 POINT I/O Dual Port EtherNet/IP Adapter Specifications POINT I/O EtherNet/IP Adapter — 1734-AENTR, Series B Attribute Value Expansion I/O capacity, max • 63 modules • 5 rack optimized connections (for digital modules only) • 31 direct connections(1) • 1734-AENTR backplane current output = 0.8 A. • Actual number of modules can vary. • Add up current requirements of modules you want to use to make sure they do not exceed the amperage limit of 0.8 A for the 1734-AENTR adapter.
1734 POINT I/O Dual Port EtherNet/IP Adapter 19 Power Supply Attribute Value Input overvoltage protection Reverse polarity protected POINTBus output current, max 5V DC @ 0.
1734 POINT I/O Dual Port EtherNet/IP Adapter General Specifications Attribute Value Isolation voltage 50V (continuous), Reinforced Insulation Type, between all circuits Type tested @ 500V AC for 60 s Field power supply 10...28.8V DC @ 10A Field power output 10...28.8V DC @ 9A Module input 10...28V DC @ 1000 mA POINTBus output, max 5V DC @ 0.8A Dimensions (HxWxD), approx. 76.2 x 73.0 x 133.4 mm (3.0 x 2.87 x 5.25 in.) Enclosure type rating None (open-style) Terminal base screw torque 0.
1734 POINT I/O Dual Port EtherNet/IP Adapter 21 Environmental Specifications Attribute Value Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock): -20...55 °C (-4...
1734 POINT I/O Dual Port EtherNet/IP Adapter Certifications Certification (when product is marked)(1) Value c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CE European Union 2004/108/EC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab.
1734 POINT I/O Dual Port EtherNet/IP Adapter 23 Notes: Publication 1734-IN041B-EN-P - October 2013
Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using its products. At http://www.rockwellautomation.com/support/, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.