Installation Instructions User guide
POINT I/O 24V dc Digital Diagnostics Input Module 19
Publication
1734-IN029A-EN-E - January 2007
Default Data Map - Configuration Assembly Instance 103
Message Size: 18 Bytes
76543210
Consume 0 Input 0 Off to On Filter Byte 0
Consume 1 Input 0 Off to On Filter Byte 1
Consume 2 Input 0 On to Off Filter Byte 0
Consume 3 Input 0 On to Off Filter Byte 1
Consume 4 Input 1 Off to On Filter Byte 0
Consume 5 Input 1 Off to On Filter Byte 1
Consume 6 Input 1 On to Off Filter Byte 0
Consume 7 Input 1 On to Off Filter Byte 1
Consume 8 Input 2 Off to On Filter Byte 0
Consume 9 Input 2 Off to On Filter Byte 1
Consume 10 Input 2 On to Off Filter Byte 0
Consume 11 Input 2 On to Off Filter Byte 1
Consume 12 Input 3 Off to On Filter Byte 0
Consume 13 Input 3 Off to On Filter Byte 1
Consume 14 Input 3 On to Off Filter Byte 0
Consume 15 Input 3 On to Off Filter Byte 1
Consume 16 Autobaud
Disable
Enable
OW3
Enable
OW2
Enable
OW1
Enable
OW0
Consume 17 Produced Assembly Instance
Produce (Tx) No produced data
Where: OW = open wire.