26 POINT I/O 24V dc Digital Diagnostics Input Module
Publication
1734-IN029A-EN-E - January 2007
Surge Transient Immunity IEC 61000-4-5:
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal
ports
Conducted RF Immunity IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80%AM from
150 kHz…80 MHz
Emissions CISPR 11: Group 1, Class A
Enclosure Type Rating
None (open-style)
North American Temp Code T5
Wire Size
0.25... 2.5 mm
2
(22...14 AWG) solid or stranded copper wire
rated at 75 °C (167 °F ) or greater
1.2 mm (3/64 in.) insulation max
Wire Category
1 - on signal ports
(1)
(1)
Use this Conductor Category information for planning conductor routing. Refer to
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Environmental Specifications
Attribute Value