Installation Instructions POINT I/O 8 Channel High Density Current Input Module Catalog Number 1734-IE8C Topic Page Important User Information 2 Environment and Enclosure 3 Prevent Electrostatic Discharge 4 European Hazardous Location Approval 5 North American Hazardous Location Approval 6 Before You Begin 7 Install the Mounting Base 8 Install the I/O Module 9 Install the Removable Terminal Block (RTB) 11 Remove a Mounting Base 11 Communicating with Your Module 12 Wiring the Input
POINT I/O 8 Channel High Density Current Input Modules Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://literature.rockwellautomation.
POINT I/O 8 Channel High Density Current Input Modules 3 Environment and Enclosure ATTENTION This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating. This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR 11.
POINT I/O 8 Channel High Density Current Input Modules Prevent Electrostatic Discharge ATTENTION This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment. • Touch a grounded object to discharge potential static. • Wear an approved grounding wriststrap. • Do not touch connectors or pins on component boards. • Do not touch circuit components inside the equipment.
POINT I/O 8 Channel High Density Current Input Modules 5 European Hazardous Location Approval European Zone 2 Certification (The following applies when the product bears the Ex Marking) This equipment is intended for use in potentially explosive atmospheres as defined by European Union Directive 94/9/EC and has been found to comply with the Essential Health and Safety Requirements relating to the design and construction of Category 3 equipment intended for use in Zone 2 potentially explosive atmospheres, g
POINT I/O 8 Channel High Density Current Input Modules North American Hazardous Location Approval The following information applies when operating this equipment in hazardous locations: Informations sur l'utilisation de cet équipement en environnements dangereux: Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only.
POINT I/O 8 Channel High Density Current Input Modules 7 Before You Begin Note that this series C product can be used with the following: • DeviceNet and PROFIBUS adapters • ControlNet and EtherNet/IP adapters, using RSLogix 5000 software, version 11 or later See the figures to familiarize yourself with major parts of the module, noting that the wiring base assembly is one of the following: • 1734-TB or 1734-TBS POINT I/O two-piece terminal base, which includes the 1734-RTB removable terminal block and 173
POINT I/O 8 Channel High Density Current Input Modules Module locking mechanism Slide-in writable label Module wiring diagram Insertable I/O module DIN rail locking screw (orange) Handle Mechanical keying (orange) Interlocking side pieces 44221 1734-TOP or 1734-TOPS one-piece terminal base with screw or spring clamp Install the Mounting Base To install the mounting base on the DIN rail, proceed as follows: 1.
POINT I/O 8 Channel High Density Current Input Modules 9 Install the I/O Module The module can be installed before, or after base installation. Make sure that the mounting base is correctly keyed before installing the module into the mounting base. In addition, make sure the mounting base locking screw is positioned horizontal referenced to the base. 1734-TB Base Turn the keyswitch to align the number with the notch. Notch position 3 is shown.
POINT I/O 8 Channel High Density Current Input Modules 1734-TOP Base Be sure the DIN-rail locking screw is in the horizontal position. Turn the keyswitch to align the number with the notch. Notch position 1 is shown. 44325 44228 1. Using a bladed screwdriver, rotate the keyswitch on the mounting base clockwise until the number required for the type of module being installed aligns with the notch in the base. 2. Make certain the DIN rail locking screw is in the horizontal position.
POINT I/O 8 Channel High Density Current Input Modules 11 Install the Removable Terminal Block (RTB) A removable terminal block is supplied with your wiring base assembly. To remove the terminal block, pull up on the RTB handle. This allows the mounting base to be removed and replaced as necessary without removing any of the wiring. To reinsert the removable terminal block, proceed as follows. 1. Insert the end opposite the handle into the base unit.
POINT I/O 8 Channel High Density Current Input Modules Install a 1734-TOPS Base 1. Position the base vertically above the installed units, such as an adapter, power supply, or existing module. 2. Slide the base down, allowing the interlocking side pieces to engage the adjacent installed unit. 3. Press firmly to seat the base on the DIN rail until the base snaps into place. 4. Verify that the DIN-rail locking screw is in a horizontal, locked position before inserting an I/O module.
POINT I/O 8 Channel High Density Current Input Modules 13 Default Data Map for the 1734-IE8C Analog Input Module Message size: 24 Bytes Byte 15 14 13 12 11 10 09 08 07 06 05 04 03 Produces Input Channel 0 High Byte (scanner Input Channel 1 High Byte Rx) Input Channel 2 High Byte Input Channel 1 Low Byte Input Channel 3 High Byte Input Channel 3 Low Byte Input Channel 4 High Byte Input Channel 4 Low Byte Input Channel 5 High Byte Input Channel 5 Low Byte Input Channel 6 High Byte Input
POINT I/O 8 Channel High Density Current Input Modules Wiring the Input Analog Module 7 3 1734 IE8C Input 0 Connection Input 1 Connection Input 2 Connection Input 3 Connection Input 4 Connection Input 5 Connection Input 6 Connection Input 7 Connection 44351 Wiring Diagram 1 0 AC or DC Current input device In 1 In 2 In 3 2 4-wire C In 0 3 4 2-wire 5 In 4 In 5 In 6 In 7 6 7 Chas Gnd In = Input channel Chas Gnd = Chassis Ground C = Common V = 12/24V DC supply Publication 1734
POINT I/O 8 Channel High Density Current Input Modules 15 Interpret the Indicators Module Status Network Status Module Status Network Status NODE: 4-20mA Analog Input Status of Input 0 0 4 Status of Input 4 Status of Input 1 1 5 Status of Input 5 Status of Input 2 2 6 Status of Input 6 Status of Input 3 3 7 Status of Input 7 44351 1734 IE8C Indicator State Description Module status Off No power applied to device Green Device operating normally Flashing green Device needs commis
POINT I/O 8 Channel High Density Current Input Modules Indicator State Description Network status Off Device is not on-line - Device has not completed dup_MAC_id test. - Device not powered - check module status indicator Flashing green Device is on-line but has no connections in the established state. Green Device on-line and has connections in the established state. Flashing red One or more I/O connections in timed-out state Red Critical link failure - failed communication device.
POINT I/O 8 Channel High Density Current Input Modules 17 Specifications IMPORTANT Note that the Input update rate and Step response for 1734-IE8C differs from that of catalog number 1734-IE2C. Input Specifications Attribute Value Number of inputs 8 analog, single-ended, non-isolated Resolution 16 bits - over 0…21 mA 0.32 μA/cnt Input current terminal 4…20 mA 0…20 mA Absolute accuracy(1) Current terminal 0.1% Full Scale @ 25 °C Accuracy drift w/temp.
POINT I/O 8 Channel High Density Current Input Modules Input Specifications Attribute Value Input impedance/resistance conversion type 60 Ω Sigma Delta Common mode rejection ratio 120 dB Normal mode rejection ratio -60 dB Notch Filter 15.7 Hz @ Notch = 60 Hz (default) 13.1 Hz @ Notch = 50 Hz 26.2 Hz @ Notch = 100 Hz 31.4 Hz @ Notch = 120 Hz 52.4 Hz @ Notch = 200 Hz 62.9 Hz @ Notch = 240 Hz 78.6 Hz @ Notch = 300 Hz 104.8 Hz @ Notch = 400 Hz 125.
POINT I/O 8 Channel High Density Current Input Modules 19 General Specifications Attribute Value Module location 1734-TB/TBS/RTB/RTBS wiring base assembly POINTBus current 75 mA Power dissipation, max 0.6 W @ 28.8V DC Thermal dissipation, max 2.0 BTU/hr @ 28.8V DC Supply voltage, backplane 5V DC Supply voltage range, field power input 10…28.
POINT I/O 8 Channel High Density Current Input Modules Environmental Specifications Attribute Value Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock): -20…55 °C (-4…131 °F) Temperature, surrounding air, max 55 °C (131 °F) Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat), IEC 60068-2-14 (Test Na, Unpa
POINT I/O 8 Channel High Density Current Input Modules 21 Environmental Specifications Attribute Value EFT/B immunity IEC 61000-4-4: ±3 kV at 5 kHz on power ports ±3 kV at 5 kHz on signal ports Surge transient immunity IEC 61000-4-5: ±1 kV line-line(DM) and ±2 kV line-earth(CM) on power ports ±2 kV line-earth(CM) on shielded ports Conducted RF immunity IEC 61000-4-6: 10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz Certifications Certification (when Value product is marked)(1) c-UL-us UL L
POINT I/O 8 Channel High Density Current Input Modules Additional Resources These documents contain additional information concerning related Rockwell Automation products. Resource Description POINT I/O Digital and Analog Modules and POINTBlock I/O Modules User Manual, publication 1734-UM001. Provides details about how to install, configure, and troubleshoot your module. You can view or download publications at http://www.literature.rockwellautomation.com.
POINT I/O 8 Channel High Density Current Input Modules 23 Notes: Publication 1734-IN033B-EN-P - November 2010
Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using its products. At http://support.rockwellautomation.com, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.