Installation Instructions User guide
POINT I/O Synchronous Serial Interface Absolute Encoder Module 15
Publication 1734-IN581D-EN-E - January 2014
Indicator Status for Modules
Status Description
Module status Off No power applied to device.
Green Device operating normally.
Flashing green Device needs commissioning due to missing, incomplete, or
incorrect configuration.
Flashing red Recoverable fault.
Red Unrecoverable fault – may require device replacement.
Flashing red/green Device is in self-test mode.
Network status Off Device is not online:
- Device has not completed dup_MAC-id test.
- Device not powered – check module status indicator.
Flashing green Device is online but has no connections in the established state.
Green Device is online and has connections in the established state.
Flashing red One or more I/O connections are in timed-out state.
Red Critical link failure – failed communication device. Device detected
error that prevents it from communicating on the network.
Flashing red/green Communication faulted device – the device has detected a network
access error and is in communication faulted state. Device has
received and accepted an Identity Communication Faulted Request
– long protocol message.
Run status Off Module is commanded to stop retrieving SSI data.
Green Module is commanded to retrieve SSI data.
Up status Off SSI data not increasing, or no SSI data is being received.
Green SSI data is increasing.
Down status Off SSI data not decreasing, or no SSI data is being received.
Green SSI data is decreasing.
Comp status Off Comparator function is not in use, or comparator value not attained.
Green Comparator value attained.
I1 status Off Latching input I1 is OFF.
Green Latching input I1 is ON.