Rockwell Automation Publication 1734-UM014B-EN-P - June 2013 27
Chapter
4
Configure the Adapter for Direct Connection
in RSLogix 5000 Software
Overview
In this example, a ControlLogix controller communicates with I/O modules via
the adapter using a direct connection.
The adapter makes a direct connection to each of the modules referenced by the
data. The modules presented in this chapter use RSLogix 5000 software, revision
11 and above.
Set Up the Hardware
In this example, a ControlLogix chassis contains the L63 controller in slot 1 and a
1756-ENBT bridge module in slot 3. The 1734-AENTR adapter is mounted on
a DIN rail in slot 0, with a 1734-OW2/C relay output module in slot 1, a 1734-
OV4E/C sink output module in slot 2, and a power supply (not shown).
ATTENTION: You must use series C POINT I/O modules with the adapter.
Series A or B POINT I/O modules do not work with the adapter.
Topic Page
Set Up the Hardware 27
Create the Example Application 29
Configure the I/O 30
Add the Local EtherNet/IP Bridge to the I/O Configuration 30
Add the POINT I/O Adapter to the I/O Configuration 33
Add the POINT I/O Modules to the I/O Configuration 35
Edit the Controller Tags 40
Create the Ladder Program 41
Download the Program to the Controller 41
Verify the Module Chassis Size 42
Configure the Adapter with Fixed IP Address 45
Recover From an Overloaded Adapter 46