Rockwell Automation Publication 1734-UM014B-EN-P - June 2013 45
Configure the Adapter for Direct Connection in RSLogix 5000 Software Chapter 4
Configure the Adapter with
Fixed IP Address
To configure the adapter with a fixed IP address to prevent the adapter from
ceasing to communicate with the ControlLogix controller:
1. All controllers with I/O connections to the AENTR and/or the modules
in its backplane need to be in program mode.
2. In the Module Properties dialog, click the Port Configuration tab.
3. Unselect the Enable DHCP box.
4. Click the Set button.
5. Read and acknowledge the warning.
6. Click OK.
7. Click the Refresh button to verify the changes.