User Manual Manual
Rockwell Automation Publication 1734-UM014B-EN-P - June 2013 47
Chapter
5
Configure the Adapter for Direct Connection
and Rack Optimization in RSLogix 5000
Software
Overview
This chapter guides you through the steps required to configure your AENTR
adapter with both direct and rack-optimized I/O connections using
RSLogix 5000 software.
You can mix I/O connection formats for different I/O modules communicating
through the same adapter. I/O modules set up to use rack optimization
communicate at the rate of the RPI configured for the adapter.
I/O modules controlled by a direct I/O connection communicate at their own set
RPI. The RPI of the rack-optimized I/O connection has no bearing on the direct
I/O connections. The modules presented in this chapter have a configuration
using RSLogix 5000 software, revision 11. The chapter contains the following
main sections
.
Topic Page
Set Up the Hardware 48
Create the Example Application 49
Configure the I/O Modules 50
Add the Local EtherNet/IP Bridge to the I/O Configuration 50
Add the I/O Adapter to the I/O Configuration 52
Add the POINT I/O Module and Configure for Rack-optimized Connection 56
Add the POINT I/O Module and Configure For Direct Connection 58
Download the Program to the Controller 60
Verify the Module Chassis Size 61
Access Module Data 64
ATTENTION: You must use series C POINT I/O modules with the
adapter. Series A or B POINT I/O modules do not work with the adapter.