Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software Chapter 5
The New Module properties dialog opens.
9. Verify that the requested packet interval (RPI) is appropriate for your
system. You use this value for the rack-optimized connection to the I/O
modules.
10. Click OK. The name of the adapter appears in the I/O tree.
IMPORTANT
To avoid overloading the adapter, we recommend that you set RPI no
less than 10 ms for rack connections and 50 ms for direct connections.