User guide
Publication 1746-UM002B-EN-P - August 2004
Specifications A-3
On-State Current Derating
Throughput and Timing
2.0 A
1.5 A
1.0 A
0.5 A
20˚C0˚C 40˚C 60˚C
Temperature
Maximum On-State Current
(per module)
Operation Description
Timing (µs)
Minimum Typical Maximum
Throughput The delay between the time the module receives a pulse and when
its real outputs and the SLC backplane are updated (based on a
count range).
300 700 1600
Input File Update
Time
The delay between the time the module receives a pulse and when
the backplane count value is updated, including setting the I/O
interrupt.
300 600 1500
Output Turn-on
Time
The time it takes for the real output to reach 90% output voltage
after commanded by the module, not including SLC scan time.
––10
Output Turn-off
Time
The time it takes for the real output to reach 10% output voltage
after commanded by the module, not including SLC scan time.
– – 100
Inductive Turn-off
Time
The time between the module receiving an input pulse and breaking
contact in a BULLETIN 110 contactor.
––50
Rate Accuracy The accuracy of the reported rate as compared to actual input rate in
the equation: reported rate/actual input rate.
– 0.005% 0.015%