INSTALL INSTRUC MOLD PRESSURE Manual

Mold Pressure Module 7
4. Configure the module with jumper plugs
Chnl Gain Jmpr 0-ref Jmpr
1 JP5 @ 450 JP1 @ 5%FS
2 JP6 @ 1 (NC) JP2 @ 0V
For this sensor Select Gain: Select 0- ref: Notes:
lo-level (2mV/V) 450 5% FS
(see Important)
Gain settings of 250 and 100 are available for
sensor sensitivities of 6 and 9 mV/V.
lo-level (4-20mA) 1 0V For 4-20mA sensors, set channel to hi-level.
bi-directional (±) 450 mid point For sensor outputs such as -100 to +100mV
hi-level (0-10V) 1 0V For gain = 1 (NC), store jumper as shown.