4. Press [F3], OTHER. For the RIO Scanner Module, enter the module ID
code. Type
13608, then press [ENTER]. (For some module ID codes, the
HHT may request additional information). The next display appears:
Rack 1 = 1746A7 7SLOT RACK
Rack 2 = NONE
Rack 3 = NONE
Slot 0 = 1747L524 CPU4K USER MEMORY
Slot 6 = OTHER 13608
F1 F2 F3 F4 F5
MOD_RCK MOD_SLT DEL_SLT UND_SLT ADV_SET
5. Press [F5], ADV_SET to view or modify the RIO scanner modules
parameters:
–––––– Advanced I/O Configuration ––––––
Current Subroutine File: 0
Current Configuration File: G6
F1 F2 F3 F4 F5
OFL
INT_SBR MOD_SET CFG_SIZ ADV_SIZ
6. Press [F4], ADV_SIZ to view or modify the I/O and M0/M1 file sizes:
–––––––– Advanced I/O Size Setup ––––––––
Note: All sizes are in words. Slot = 6
Output Size: 32 M0 File Size: 0
Input Size: 32 M1 File Size: 0
Scanned Output Size: 32
Scanned Input Size: 32
ENTER SCANNED OUTPUT: 32
F1 F2 F3 F4 F5
OFL
The default for the scanned output size is 32 words. In this example, to
reduce the processor scan time, enter 16 words.
7. Type
16, then press [ENTER].
The display changes as follows:
–––––––– Advanced I/O Size Setup ––––––––
Note: All sizes are in words. Slot = 6
Output Size: 32 M0 File Size: 0
Input Size: 32 M1 File Size: 0
Scanned Output Size: 16
Scanned Input Size: 32
ENTER SCANNED INPUT: 32
F1 F2 F3 F4 F5
OFL
8. View or modify the remaining parameters by pressing [ENTER]. See the
Remote I/O Scanner User Manual, catalog number 1747NM005, for