Chapter 24
Sequencer Instructions
248
Status Bits
EN (bit 15) The enable bit. This bit is set on a false-to-true transition
of the SQL rung and reset on a true-to-false transition.
DN (bit 13) The done bit. This bit is set after the instruction has
operated on the last word in the sequencer load file. It is reset on the next
false-to-true rung transition after the rung goes false.
ER (bit 11) The error bit. This bit is set when the processor detects a
negative position value, or a negative or zero length value. This results in
a major error if not cleared before the END or TND instruction is
executed. Use an OTU with address S:5/2 to avoid a CPU fault.
Length (word 1) This is the number of steps of the sequencer load file
(and also of the source if the source is a file address), starting at position
1. Position 0 is the startup position. The instruction automatically resets
(wraps) to position 1 at each cycle completion.
The position address assigned for a sequencer file is step zero. Sequencer
instructions use length plus 1 word of data for each file referenced in the
instruction. This applies to the source if addressed as a file.
A length value that points past the end of the programmed file causes a
runtime major error to occur. If you alter a length value with your ladder
program, make certain that the altered value is valid.
Position (word 2) This is the word location or step in the sequencer file
to which data is moved.
A position value that points past the end of the programmed file causes a
runtime major error to occur. If you alter a position value with your
ladder program, make certain that the altered value is valid.