User guide

Chapter 27
The Status File
2718
Fault Classification Processor
Description User
Address
Error
Code
(Hex)
Powerup Errors Non-User Non-Recov Recov 5/02
5/01,
Fixed
S:6
0001 NVRAM error.
X
0002 Unexpected hardware watchdog timeout.
X
0003 Memory module memory error.
X
0004 Memory integrity check failed (runtime).
X
Fault Classification Processor
Description User
Address
Error
Code
(Hex)
Going to Run Errors Non-User Non-Recov Recov 5/02
5/01,
Fixed
S:6 0010
Processor does not meet proper revision level.
X
0011
The executable file number 2 is absent.
X
0012
The ladder program has a memory error.
X
0013 The required memory module is absent or either S:1/10 or
S:1/11 is not set (and the program requires it).
X
0014
Internal file error.
X
0015
Configuration file error.
X
0016 Startup protection after power loss. Error condition exists at
powerup when bit S:1/9 is set and powerdown occurred while
running.
X