ERROR CODES: The characters xx in the following
codes represent the slot number, in hex. The characters
xx become 1F if the exact slot cannot be determined.
RECOVERABLE I/O FAULTS (SLC 5/02 processors
only): Many I/O faults are recoverable. To recover, you
must disable the specified slot, xx, in the user fault
routine. If you do not disable slot xx, the processor will
fault at the end of the scan.
Slot xx
000
101
202
303
404
505
606
707
Slot xx
808
909
10 0A
11 0B
12 0C
13 0D
14 0E
15 0F
Slot xx
16 10
17 11
18 12
19 13
20 14
21 15
22 16
23 17
Slot xx
24 18
25 19
26 1A
27 1B
28 1C
29 1D
30 1E
SLOT NUMBERS (xx) IN HEXADECIMAL
Error Code
(Hex)
Description Probable Cause Recommended Action
xx50 A rack data error is detected.
•Either noise,
•lightning,
•improper grounding,
•lack of surge suppression on outputs
with inductive loads, or
•poor power source.
Correct the problem, clear the fault, and
re-enter Run mode.
xx51 A “stuck” runtime error is detected on an
I/O module.
If this is a discrete I/O module, this is a
noise problem. If this is a specialty I/O
module, refer to the applicable user
manual for the probable cause.
Cycle power to the system. If this does not
correct the problem, replace the module.
xx52 A module required for the user program is
detected as missing or removed.
An I/O module configured for a particular
slot is missing or has been removed.
•Either disable the slot in the status file
(S:11 and S:12), or
•Insert the required module in the slot.
xx53 At going-to-run, a user program declares a
slot as unused, and that slot is detected as
having an I/O module inserted.
This code can also mean that an I/O
module has reset itself.
•Either the I/O slot is not configured for a
module, but a module is present, or
•the I/O module has reset itself.
•Either disable the slot in the status file
(S:11 and S:12), clear the fault and run,
•Remove the module, clear the fault and
run, or
•modify the I/O configuration to include
the module, then reload the program
and run.
•If you suspect that the module has reset
itself, clear the major fault and run.
xx54 A module required for the user program is
detected as being the wrong type.
An I/O module in a particular slot is a
different type than was configured for that
slot by the user.
•Either replace the module with the
correct module, clear the fault, and run,
or
•change the I/O configuration for the slot,
reload the program and run.