User guide
5/02 Processor Only
Chapter 29
Understanding the User Fault Routine –
29–2
Recoverable User Faults
GOING TO RUN ERRORS
0013
The required memory module is absent or either S:1/10 or S:1/11 is not set
(and the program requires it).
0016
Startup protection after power loss. Error condition exists at powerup when
bit S:1/9 is set and powerdown occurred while running.
RUNTIME ERRORS
0020 A minor error bit is set at the end of the scan.
0029
Indexed address reference outside of entire data file space (range of B3:0
through the last file).
INSTRUCTION ERRORS
0032 Sequencer length/position points past end of data file.
0033 Length of LFU, LFL, FFU, FFL, BSL, or BSR points past end of data file.
0034 A negative value for a timer accumulator or preset value was detected.
0036
Invalid value for a PID parameter. Code 0036 is discussed further in
chapter 26.