User guide

5/02 Processor Only
Chapter 29
Understanding the User Fault Routine
293
I/O ERRORS
Recoverable only if you disable slot xx in the
user fault routine
xx50 A rack data error is detected.
xx52 A module required for the user program is detected as missing or removed.
xx53
At going-to-run, a user program declares a slot as unused, and that slot is
detected as having an I/O module inserted. Can also mean that the I/O
module has reset itself.
xx54
A module required for the user program is detected as being the wrong
type.
xx55
A module required for the user program is detected as having the wrong
I/O count or wrong I/O driver.
xx57
A specialty I/O module has not responded to a lock shared memory
command within the required time limit.
xx59
A specialty I/O module has not responded to a command as being
completed within the required time limit.
xx5A Hardware interrupt problem.
xx5B
G file configuration error User program G file size exceeds capacity of the
module.
xx5C
M0M1 file configuration error User program M0M1 file size exceeds
capacity of the module.
xx5D Interrupt service requested is not supported by the processor.
xx5E Processor I/O driver (software) error.
xx60
thru
xx6F
Identifies an I/O module specific recoverable major error. Refer to the user
manual supplied with the module.