A-2 Local Database Access Using PLC-5 MSG Instructions
Data-table address in destination processor - The destination
file must be N7, otherwise the request will be rejected.
PLC-5 Typed Read and PLC-5 Typed Write: N7:XX
where XX is the zero-based element offset in the Local
Database file
PLC-2 Unprotected Read, PLC-2 Unprotected Write: YY
where YY is the octal zero-based element offset in the Local
Database file
Port number - set to 2 for the ControlNet network
Flags:
.TO - forces a message to timeout
.EW - indicates that the message is waiting for an open
connection
.CO - indicates that the message is sent
.ER - indicates that the message was terminated due to an
error
.DN - indicates that the message was sent without error
.ST - indicates that the message was started
.EN - indicates that the message instruction is enabled
Error code – indicates the error when the .ER is set
For each concurrently enabled MSG instruction, the PLC-5 processor
opens an unscheduled connection.
All messages sent over different connections to the 1747-SCNR
scanner have the same priority.