Environmental Specifications
Attribute 1752-L24BBB 1752-L24BBBE
Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
-40…70 °C (-40…158 °F)
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-10…55 °C (14…131 °F) (surrounding air temperature)
Relative humidity IEC 60068-2-30
(Test Db, Unpackaged Nonoperating Damp Heat):
10…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating):
0.35 mm @ 10…57 Hz
5 g @ 57…150 Hz
IEC 60068-2-6 (Test Fc, Operating):
5 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock): 15 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock): 30 g
Enclosure type rating Meets IP20
Emissions CISPR 11: Group 1, Class A
ESD immunity IEC 61000-4-2:
• 4 kV contact discharges
• 8 kV air discharges
IEC 61000-4-2:
• 6 kV contact discharges
• 8 kV air discharges
Radiated RF immunity IEC 61000-4-3:
• 10 V/m with 1 kHz
sine-wave 80% AM from
80…1000 MHz
• 10 V/m with 1 kHz
sine-wave 80% AM from
1.4…2.0 GHz
• 10 V/m with 200 Hz 50%
Pulse 100% AM at 900 MHz
• 10 V/m with 200 Hz 50%
Pulse 100% AM at 1200
MHz
• 3 V/m with 1 kHz sine-wave
80% AM from 2000…2700
MHz
IEC 61000-4-3:
• 10 V/m with 1 kHz
sine-wave 80% AM from
80…1000 MHz
• 10 V/m with 1 kHz
sine-wave 80% AM from
1.4…2.0 GHz
• 20 V/m with 200 Hz 50%
Pulse 100% AM at 800, 900,
1200 MHz
• 3 V/m with 1 kHz sine-wave
80% AM from 2000…2700
MHz