Installation Instruction Manual

8 SmartGuard 600 Controllers
Publication 1752-IN001C-EN-P - January 2009
Set the communication rate by using the DIP switch on the front of the controller.
Set the IP Address for Ethernet Communication
Connect the 1752-L24BBBE controller to the network via a 100 Mbps Ethernet
switch, which will help reduce collisions and lost packets, and increase bandwidth.
The 1752-L24BBBE controller is shipped with BOOTP enabled for setting the IP
address. You can use any commercially available BOOTP server. If you do not have
BOOTP Server capabilities on your network, download the free Rockwell
Automation BOOTP server from http://www.ab.com/networks/bootp.html
.
To set the IP address by using the Rockwell Automation BOOTP utility, follow
these steps.
1. Run the BOOTP utility.
2. Double-click the hardware address of the device you want to configure.
DIP Switch Settings
DIP Switch
Pin
1 2 3 4 Communication Rate
OFF OFF OFF OFF 125 Kbps
ON OFF OFF OFF 250 Kbps
OFF ON OFF OFF 500 Kbps
ON ON OFF OFF Set by software
ON or OFF ON or OFF ON OFF Set by software
ON or OFF ON or OFF ON or OFF ON Automatic baud-rate detection
IMPORTANT
If you change the communication rate of your network, make sure that all devices change
to the new communication rate. Mixed communication rates produce communication
errors.