User Manual

Rockwell Automation Publication 1752-UM001E-EN-P - June 2014 181
Monitor Status and Handle Faults Chapter 12
2. Click the EtherNet/IP Error History tab.
a. Click Save to save the error history data, which can also be saved in a
separate CSV file.
b. Click Clear to erase the error history saved in the controller.
c. Click Update to refresh the error history information.
Ethernet Error History Table
Error Code Error Detail Code 7-segment Display
1st Byte
(1)
2nd Byte
(1)
0602 CPU Bus Unit Memory 01: Read error Variable E9<->n4
02; Write error
020F Communications Controller 00 01 F4<->n4
0211 Duplicate IP Address 02 Lower byte of IP address F0<->n4
021A Logic Error in Setting table 00 Variable UF
03C4 Server Connection 04;BOOTP 01; Specific host does not exist E3<0>n4
07: Transmission error
08: Reception error
0A: Obtaining IP address error