Logic Functions Command Reference Appendix C
Routing Instruction
The Routing instruction routes one input signal to a maximum of eight output
signals. It is used to output a signal to more than one physical address, such as an
output tag. The number of outputs can be set by using the I/O Setting tab in the
Function Block Properties dialog box. The default setting is one.
Routing Instruction Diagram
Routing Instruction Truth Table
In the truth table, 0 is off and 1 is on.
Reset Set Flip-flop (RS-FF)
Instruction
When the input signal is on, the Output Enable signal is turned on. The Output
Enable signal stays on even if the input signal turns off. When the Reset signal is
on, the Output Enable signal turns off.
A Fault Present output can also be used in programming. To enable this optional
output, check the Use Fault Present checkbox on the I/O Settings tab of the
Function Block Properties dialog box in RSNetWorx for DeviceNet software.
Reset Set Flip-flop Instruction Diagram
Output 1Input 1
Table C.3 Truth Table for Routing Evaluation
Input 1 Output 1 Output 2 Output 3 Output 4 Output 5 Output 6 Output 7 Output 8
000000000
111111111
!
Output EnableInput
Reset
Default Connections Maximum Inputs for Reset Set Flip-Flop Function
Output EnableInput
Reset Fault Present