User Manual

Rockwell Automation Publication 1752-UM001E-EN-P - June 2014 269
Explicit Messages Appendix E
SV for Test
Output Total On
Time or Contact
Operation
Counter
Read Reads the SV of the total on time
or contact operation counter for
the input (1…4) specified by the
Instance ID.
0E hex 35B hex 01…04 hex 86 hex
4 bytes
0000 0000 to
FFFF FFFF hex
(0 to 4,294,967,295)
Write Writes the SV of the total on time
or contact operation counter for
the input (1…4) specified by the
Instance ID.
10 hex 35B hex 01…04 hex 86 hex 4 bytes
0000 0000…
FFFF FFFF hex
(0…
4,294,967,295)
Read Test Output
Total On Time or
Contact
Operation
Counter
Read Reads the total on time or
contact operation counter for the
input (1…4) specified by the
Instance ID.
0E hex 35B hex 01…04 hex 84 hex
4 bytes
0000 0000
FFFF FFFF hex
(0… 4,294,967,295)
Reset Test Output
Total On Time or
Contact
Operation
Counter
Reset Resets to 0 the total on time or
contact operation counter for the
test output (1…4) specified by
the Instance ID.
05 hex 35B hex 01…04 hex 84 hex
——
Read Monitor
Status of Test
Output Total on
Time or Contact
Operation
Counter
Read Reads the monitor status of the
total on time or contact
operation counter for the test
output (1…4) specified by the
Instance ID.
0E hex 35B hex 01…04 hex 85 hex
1 byte
00 hex: in range
01 hex: out of range (over
monitor value)
Read Test Output
Safety Flag
Read Reads the normal flag status for
the test output (1…4) specified
by the Instance ID.
0E hex 35B hex 01…04 hex 68 hex
1 byte
00 hex: normal
01 hex: error
Read Test Output
Error Information
Cause
Read Reads the cause for the normal
flag of the test output (1…4)
specified by the Instance ID being
off (error).
0E hex 35B hex 01…04 hex 76 hex
1 byte
00 hex: no error
01 hex: invalid
configuration
02 hex: overcurrent
detection
05 hex: high constant error
06 hex: undercurrent
detection
Read OR of Test
Output Safety
Flags
Read Reads the logical OR of the
normal flag for all test outputs
(1…4).
0E hex 35C hex 01 hex 69 hex
1 byte
00 hex: all normal
01 hex: error
Read OR of
Monitor Status of
Test Output Total
On Times or
Contact
Operation
Counters
Read Reads the logical OR of the
monitor status of the total on
time or contact operation counter
for all test outputs (1…4).
0E hex 35C hex 01 hex 72 hex
1 byte
00 hex: all in range
01 hex: test output out of
range (over monitor value)
Table 44 - Monitoring Test Output Terminals
Explicit
Message
Service Function
Command
Response
Service
Code
Class
ID
Instance ID Attribute
ID
Data Size