371 Mtr OL Trip Cnfg
Enter a value to configure the drive's response to a “Motor
Overload Trip” exception event.
Value 0 - Ignore configures the drive module to
continue running as normal, in response to this event
Value 1 - Alarm configures the drive module to set the
appropriate alarm bit in response to this event
Value 2 - FltCoastStop configures the drive module to
perform a coast stop and set the appropriate fault bit in
response to this event
Value 3 - FltRampStop configures the drive module to
perform a ramp stop and set the appropriate fault bit in
response to this event
Value 4 - CurLimStp configures the drive module to
perform a current limit stop and set the appropriate
fault bit in response to this event
Default Val 2 FltCoastStop
Options: Val 0
Val 1
Val 2
Val 3
Val 4
Ignore
Alarm
FltCoastStop
FltRampStop
FltCurLimStp
File:
Group:
Utility
Fault/Alm Config
372 Mtr OL Pend Cnfg
Enter a value to configure the drive's response to a “Motor
Overload Pending” exception event.
Value 0 - Ignore configures the drive module to
continue running as normal, in response to this event
Value 1 - Alarm configures the drive module to set the
appropriate alarm bit in response to this event
Value 2 - FltCoastStop configures the drive module to
perform a coast stop and set the appropriate fault bit in
response to this event
Value 3 - FltRampStop configures the drive module to
perform a ramp stop and set the appropriate fault bit in
response to this event
Value 4 - CurLimStp configures the drive module to
perform a current limit stop and set the appropriate
fault bit in response to this event
Default Val 1 Alarm
Options: Val 0
Val 1
Val 2
Val 3
Val 4
Ignore
Alarm
FltCoastStop
FltRampStop
FltCurLimStp
File:
Group:
Utility
Fault/Alm Config
373 Motor Stall Time
Enter or write a value to specify the time delay between when
the drive detects a “Motor Stall” condition and when it
declares the exception evet.
Units:
Default:
Min:
Max:
Type:
File:
Group:
Sec
5
0.1
3000
Linkable, Read-Write, Floating Point
Utility
Fault/Alm Config
374 Motor Stall Cnfg
Enter a value to configure the drive's response to a “Motor
Stall” exception event.
Value 0 - Ignore configures the drive module to
continue running as normal, in response to this event
Value 1 - Alarm configures the drive module to set the
appropriate alarm bit in response to this event
Value 2 - FltCoastStop configures the drive module to
perform a coast stop and set the appropriate fault bit in
response to this event
Default Val 0 Ignore
Options: Val 0
Val 1
Val 2
Ignore
Alarm
FltCoastStop
File:
Group:
Utility
Fault/Alm Config
No. Name
Description
Values