B-148 1756-DMD30 Speciļ¬c Information
2163 CML Ref Rate
Controls the current reference ramp block within the PMI
processor. Leave at default for most applications, which sets
the rate equal to parameter 354[Curr Rate Limit].
Default:
Min:
Max:
Type:
File:
Group:
4095
1
4095
Linkable, Read-Write, 16-bit Integer
DPS/PMI
Motor Data
2180 Motor NP RPM
Set to the motor nameplate rated RPM.
Units:
Default:
Min:
Max:
Type:
File:
Group:
RPM
1750
1
30000
Non-Linkable, Read-Write, 16-bit Integer
Torque Control
Current
2181 Overspd Trip Pt
Set the overspeed trip point for overspeed detection in the PMI
processor.
Units:
Default:
Min:
Max:
Type:
File:
Group:
RPM
2000
1
30000
Non-Linkable, Read-Write, 16-bit Integer
DPS/PMI
Motor Data
2182 Motor NP FLA
Set to the motor nameplate full load amps.
Units:
Default:
Min:
Max:
Type:
File:
Group:
Amps
1
1
3276.7
Non-Linkable, Read-Write, 16-bit Integer
DPS/PMI
Motor Data
2183 Motor NP Volts
Set to the motor nameplate rated volts.
Units:
Default:
Min:
Max:
Type:
File:
Group:
Volt
1
1
32767
Non-Linkable, Read-Write, 16-bit Integer
DPS/PMI
Motor Data
2184 PMI Curr Lim
Provides positive and negative current limit values within the
PMI processor. If this value is les than parameter 120[Current
PosLimit] and the absolute value of parameter 119 [Current
NegLimit], this value will set both the positive and negative
actual current limits.
Units:
Default:
Min:
Max:
Type:
File:
Group:
%
100
100
400
Non-Linkable, Read-Write, 16-bit Integer
DPS/PMI
Motor Data
2185 Hot Field Curr
Set to the Hot Amps value on the motor nameplate.
Units:
Default:
Min:
Max:
Type:
File:
Group:
Amps
0.10
0.01
327.67
Non-Linkable, Read-Write, 16-bit Integer
Speed Control
Regulator
No. Name
Description
Values