Publication 1756-UM522B-EN-P - February 2003
1756-DMD30 Specific Information B-149
2186 Min Field Curr
Set to the minimum amps value on the motor nameplate.
Units:
Default:
Min:
Max:
Type:
File:
Group:
Amps
0.10
0.01
99.99
Non-Linkable, Read-Write, 16-bit Integer
DPS/PMI
Motor Data
2187 Field Loss Amps
Set the under-current trip point for field loss detection in the
PMI processor.
Units:
Default:
Min:
Max:
Type:
File:
Group:
Amps
0.10
0.01
99.99
Non-Linkable, Read-Write, 16-bit Integer
Speed Control
Regulator
2188 Field Off Delay
Set the amount of time the field will remain energized after a
fault condition. (1 to 300S)
Units:
Default:
Min:
Max:
Type:
File:
Group:
Sec
180
1
300
Non-Linkable, Read-Write, 16-bit Integer
DPS/PMI
Motor Data
2189 Motor Inertia
The time, in seconds, for the motor (not coupled to load) to
accelerate from zero to base sped, at rated motor torque. The
drive calculates Motor Inertia during the auto-tune procedure.
Units:
Default:
Min:
Max:
Type:
File:
Group:
Sec
0.4
0.01
655
Linkable, Read-Write, Floating Point
DPS/PMI
Drive Config
2190 Total Inertia
The time, in seconds, for a motor coupled to a load to
accelerate from zero to base speed, at rated motor torque. The
drive calculates Total Inertia during the auto-tune procedure.
Units:
Default:
Min:
Max:
Type:
File:
Group:
Sec
2
0.01
655
Linkable, Read-Write, Floating Point
DPS/PMI
Drive Config
No. Name
Description