User guide
FACTORYTALK HISTORIAN ME MODULE USER’S GUIDE
100
Log Threshold Configuration
The Log Threshold Configuration section allows you to specify a warning level for
log files. The range is 95-99%, and the default is 95%.
When the log storage reaches its configured threshold, the FactoryTalk Historian ME
deletes older log files and logs a message in the System Log page:
“<full path> has been removed because the /mnt/log partition is
full.”
Archive Disk Threshold Configuration
The Archive Disk Threshold Configuration section allows you to specify a warning
level for archive disk usage. The range is 95-99%, and the default is 95%.
When the archive disk reaches its configured threshold, FactoryTalk Historian ME
stops Data Collection and logs a message in the System Log page:
“Stopping Data Collection because one or more partitions is full.”
It also deletes pimesslogfile located under /mnt/appdata/dat and logs a message in the
System Log page:
“<full path> has been removed because the /mnt/appdata partition is
full.”
Stopping Data Collection allows the module to process events from transient event
files to archive storage and make more storage space available.