Chapter 8 Monitor and Maintain an Enhanced Redundancy System
Synchronization After a Switchover
To monitor the synchronization of your system after you initiate the test
switchover, you can monitor the synchronization process by using these methods:
Click the Synchronization Status tab and monitor the
Secondary Readiness column. The states No Partner, Disqualified,
Synchronizing, and Synchronized indicate the stages of synchronization.
View the module status display of a primary communication module. The
states PwNS, PsDS, PwQg and PwQS indicate the stages of
synchronization.
View the module status display of the secondary redundancy module. The
states DISQ, QFNG, and SYNC indicate the stages of synchronization.
TIP
If your Auto-Synchronization parameter is set to Always,
your system begins synchronizing immediately after the
switchover.