User Manual Owner's manual

Rockwell Automation Publication 1756-UM535D-EN-P - November 2012 33
Design an Enhanced Redundancy System Chapter 2
Plan for Communication Module Connections
A CIP connection is a point-to-point communication mechanism used to
transfer data between a producer and a consumer. These are examples of CIP
connections:
Logix5000 controller message transfer to Logix5000 controller
I/O or produced tag
Program upload
RSLinx DDE/OPC client
PanelView™ polling of a Logix5000 controller
ControlLogix ControlNet communication modules provide 131 total CIP
connections. Consider these points when using CIP connections with
ControlLogix ControlNet communication modules:
Three of the 131 CIP connections are reserved for redundancy. The three
redundant-system CIP connections always appear to be in use, even when
no connections are open.
You can use the remaining 128 CIP connections in any manner that your
application requires, such as the examples listed above.
ControlLogix EtherNet/IP communication modules provide 259 total CIP
connections. Consider these points when using CIP connections with
ControlLogix EtherNet/IP communication modules:
Three of the 259 CIP connections are reserved for redundancy.
You can use the remaining 256 connections in any manner that your
application requires, such as the examples listed above.