Configuration Manual Owner manual

Publication 1757-PM002A-EN-E - June 2006
Troubleshooting 5-3
A Red X is on the linking
device in the HSE/H1
window.
The Device Id may not be
associated in the linking
device's attributes.
Refer to Initialize Communications
and Associate the FFLD on
page 4-23.
A Red X is on a fieldbus
device in the H1 window.
The Device Id may not be
associated in the Device's
attributes.
Refer to Initialize Communications
and Associate the FFLD on
page 4-23.
Online characterization
doesn't show any real-time
values.
Strategy is not
downloaded.
Download the devices associated
with the strategy. Refer to
Download the Configuration on
page 4-37.
Tags are not exported. Refer to Export Tags on page 4-37.
Online CM monitor
parameter tags are gray
and have no values.
Tags are not exported. Refer to Export Tags on page 4-37.
Unable to download after
adding new device to an
existing strategy.
Macro-Cycle value on H1
network may be too low.
Increase the macrocycle time on the
H1 network(s). Refer to the
Macrocycles section of the
RSFieldbus User Manual, publication
RSFBUS-UM001A-EN-E.
Red Links on the Strategy
after a successful
download.
Links are not properly
established.
Update H1 device and re-download
device. To update a device,
right-click it and select Update.
Download error Communication error Update H1 device associated with
error message and redownload the
device.
Update H1 device and re-download
device. To update a device,
right-click it and select Update.
Schedule download failure Communication error Right-click the H1 and select
Download Schedule.
Logix block inputs and
outputs are red.
CLX is not in run mode. Put the CLX in Run Mode.
Yellow triangles on Logix
blocks in the I/O tree in
RSLogix.
Mismatched SLOT
number
Match the SLOT number in the Logix
block with configuration in CLX.
Refer to Add Your Logix Block on
page 4-45.
NS LED blinking green Communication not
configured on RSLogix or
RSFieldbus
Refer to Configure Communication
Settings on page 4-23.
Assign tag failure Communication error Verify tag assignment.
Refer to Assign Tags on page 4-27.
"Capabilities File
Information missing" error
message
Device revision/ DD
revision mismatch
Verify proper device revision/DD
revision selections. Right-click the
corresponding icon and select
Attributes.
Symptom Possible Problem Solution