Configuration Manual Owner manual

Publication 1757-PM002A-EN-E - June 2006
5-8 Troubleshooting
Is There Power on the H1 Network?
No:
a. Connect a power supply to the network.
Is the Power Supply Connected Through a Proper Power Conditioner?
No:
a. Use a proper power conditioner in accordance with the Foundation
Fieldbus Installation Guide.
Power must be applied to the network through a proper power
conditioner. The power supply cannot be directly connected to the H1
network.
Is There Network Power on the Linking Device Network Connector?
No:
Is There Power on the Terminal or Network Connector Block/Power on the
Output on the Power Conditioner?
No:
a. Repair or replace the power conditioner.
Is the Voltage at the Output of the Power Conditioner 11-30 VDC?
No:
a. Repair, replace or adjust the power supply.
Is the RSFieldbus Project Properly Configured?
Don’t know:
a. Refer to Create A New RSFieldbus Project on page 4-14 and
configure a project or use a known good project file to test the
operation of the linking device on the H1 network. If this does not
work, contact Tech Support for assistance in building a proper
project file.
Yes:
a. Remove power from the linking device.