5-10 Troubleshooting
What To Do if the Linking
Device Blinks On and Off in
the H1 Live List
Is The Linking Device Properly Connected to the Network?
a. Verify that there are two and only two terminators on the network.
b. Verify that the polarity of the network cabling is consistent (i.e. red to
red and black to black).
c. Verify that the network voltage is between 11 and 30 VDC.
Are There Any Other Devices on the H1 Network?
Yes:
Disconnect any other devices from the network:
a. Remove power from the linking device.
b. On the top of the linking device move the jumper to the left-most
contact position then back to the right-most contact position.
c. Close RSFieldBus.
d. On the PC Host in the c:\Program Flies\Rockwell
Software\RSFieldbus\OLEServers\ directory delete the
IDShellHSE.bin file.
e. Restart RSFieldBus.
f. Load your project.
g. Apply power to the linking device. Allow the linking device to
completely start up as indicated by the H1 channel activity LEDs
blinking.
h. Go online in RSFieldBus and monitor the H1 LiveList.
Does the Linking Device Appear in the H1 Live List Now?
No:
a. Contact tech Support.
Or:
a. Re-connect the individual nodes one at a time.
b. As each device is connected, verify the device appears in the H1 Live
list and that the linking device remains in the H1 live list.
Do All Devices and the Linking Device Appear in the H1 Live List?
Yes: Done.
No:
a. Contact Tech Support.