Troubleshooting 5-11
Or:
There is only the linking device on the network:
a. Remove power from the linking device
b. On the top of the linking device, move the jumper to the left-most
contact position then back to the right-most contact position.
c. Close RSFieldBus.
d. On the PC Host in the c:\Program Flies\Rockwell
Software\RSFieldbus\OLEServers\ directory delete the
IDShellHSE.bin file.
e. Restart RSFieldBus.
f. Load your project.
g. Apply power to the linking device. Allow the linking device to
completely start up as indicated by the H1 channel activity LEDs
blinking.
h. Go online in RSFieldBus and monitor the HSE LiveList.
Does the Linking Device Appear in the H1 Live List Now?
Yes: Done.
No:
a. Contact tech Support.
What To Do if You are
Unable to See Parameter
Values in the Function
Block Online
Characterization
a. Verify that tags have been exported.
b. Export Tags.
c. Verify that the HSE download has completed.
d. Do an HSE download.
e. Verify that the H1 download has completed.
f. Do an H1 network download.
Are the Parameter Values Displayed Now?
Yes: Done
No:
a. Perform an UPDATE command on the device.
Are the Parameter Values Displayed Now?
Yes: Done