5-12 Troubleshooting
No:
a. Save the project.
b. Close the project.
c. Close RSFieldbus.
d. Verify that the RSFieldbus servers close.
e. End the servers execution if not closed.
f. On the PC Host in the c:\Program Flies\Rockwell
Software\RSFieldbus\OLEServers\ directory delete the
IDShellHSE.bin file.
g. Start RSFieldbus.
h. Load the project file.
i. Go online.
j. Do online characterization for a function block.
Are the Parameter Values Displayed Now?
Yes: Done.
No:
a. Remove power from the linking device
b. On the top of the linking device move the jumper to the left-most
contact position then back to the right-most contact position.
c. Apply power to the linking device. Allow the linking device to
completely start up as indicated by the H1 channel activity LEDs
blinking.
d. Go online in RSFieldbus
e. Perform an HSE download
f. Perform an H1 download.
g. Do online characterization for a function block.
Are the Parameters Values Displayed Now?
Yes: Done.
No:
a. Contact Tech Support.