B-4 RSFieldbus Remote Access
5. Change the Type of Access to Allow Access for the following:
a. Servers and Clients - Administrator, Everyone, INTERACTIVE,
SYSTEM
b. Domain Clients - (Server computer name)\Administrators, Domain
Users, NETWORK
c. Domain Servers - (Client computer name)\Administrators, Domain
Users, NETWORK
6.Click OK.
7. Repeat steps 5–6 for the Default Launch Permissions.
8. Select the Applications tab and double-click Rockwell Software OPC &
Conf Server for HSE.
9. Select the Location tab and complete the following:
a. Check the Run application on this computer check box.
b. For Clients, check the Run application on the following computer
check box and click Browse to locate the Server name on the
network.
This allows the Client to use the service on the Server.
If you are unable to browse for the Server, verify that you can PING
the Server by IP address and name.
10.Select the Security tab and verify that access and launch permissions are set
to default.
11. Select the Identity tab.
a. For Servers, select The interactive user.
b. For Clients, select The launching user.
12.Click OK on the Rockwell Software OPC & Conf Server for HSE
Properties and the Distributed COM Configuration Properties
windows.