RSFieldbus Remote Access B-5
Verify RSView Remote Access
To verify that the settings are correct, create a graphic in the Client machine,
which has the RSView software installed. When you attempt to change a
parameter of function block that is loaded and in operation, you should
observe the following:
1. When the RSView Client attempts to connect to the RSFieldbus Server,
it will launch the RS HSE OLE Server and the RS DD Server, which
appear in the system tray of the Local Server. The launching of these
servers can be also verified by observing the appearance of
RSddserver.exe and RSHseServer.exe in Task Manager (if they were not
running initially).
2. You should be able to change the MODE of a function block using a
numeric entry. The function block parameters have a numeric
association that may not be available to the user. The online
characterization of a function block within RSFieldbus can be used to
provide the hex numeric data. You can display the hex value association
by toggling the Show value as symbol button located in the On line
Characterization window.
3. When the RSView Client attempts to disconnect from the RSFieldbus
Server, it will stop the RS HSE OLE Server and the RS DD Server,
which will be removed from the system tray of the Local Server (if they
were not being actively used by the RSFieldbus Server for online
monitoring).
Define the OPC Server on RSView Studio
1. On the remote machine, select Start Programs Rockwell Software
RSView Enterprise RSView Studio.
The Licensing System Information window shows how many Blocks are
licensed on your system.
2. At the Product Type Selection window, select SE Stand-alone for
non-domain machines or SE Distributed for domain-based machines.
3. Click Continue.
The New/Open SE Stand-alone Application window opens.
4. On the New tab, enter an application name click Create.
RSView Studio opens.