B-6 RSFieldbus Remote Access
5. On the RSView Studio menu bar, click File New OPC.
An OPC DATA Server Properties window opens.
6. In the Name field, enter >RSFieldbus<.
7. Select Server will be hosted on remote computer and click Browse to
find the Server.
8. Select the Server and click OK.
9. At the OPC Server name (ProgID) field, click Browse to find the OPC
Server running on the Server machine.
10. Select the Rockwell Software OPC & Conf Server and click OK.
11. Click OK to close the Properties window.
The computer attempt to establish a connection, and the message
window at the bottom of RSView Studio indicates progress.
Remote RSFieldbus
Configuration Access
The architecture for this case is shown below.
The laptop is a temporary connection to the network whose sole purpose is to
update the control strategy.
RSFieldbus
Windows 2000 SP4
1757-FFLD
STATUS
WDOG
BATT
NS 1
MODE
H1
H1
H1
H1
H1-1
H1-2
H1-3
H1-4
FOUNDATION Fieldbu s
FOUNDATIO N Fieldbus
Linking Device
RSFieldbus
Windows 2000 SP4
Temporary
Laptop
HSE Network TCP/IP
H1 Network