Configuration Manual Owner manual

Publication 1757-PM002A-EN-E - June 2006
RSFieldbus Remote Access B-7
DCOM Settings
Following the instructions in Server and Client DCOM Settings on page 3 to
set up the desktop as the Server and the laptop as the Client.
Before you Begin
Verify that the Program Files folder on the Local Server is set up for
sharing.
Verify that the same DDs exist on both the Local Server and the
Remote Client.
Remote Access
In this scenario your are using a project, created and stored on the Local
Server, and opening it on the Remote Client (laptop).
1. From the RSFieldbus main window on the Remote Client, select Project
File
Open and browse to the Local Server.
2. Select the project and click Open.
The project opens.
3. Right-click the Fieldbus Networks icon and select Communication
Settings.
The Communication Settings window opens.
4. Under Server Context, select Remote.
5. In the Node Name field, enter >\\(Local Server name)<
This causes communications to use the Local Server's services for
configuration and monitoring.
6. Edit the project as needed.
7. When you are ready to export tags, right-click the project icon and select
Export Tags.
8. Locate the TagInfo.ini file in the OLE Servers directory located on the
Local Server machine.