Configuration Manual Owner manual

Publication 1757-PM002A-EN-E - June 2006
Set Up A System 2-25
However, it is still best to call RA Tech Support (see page 1-6) if this situation
occurs, and for other problems concerning DHCP.
H1
H1 Fieldbus is a digital, serial, multidrop data bus for communication with
industrial devices or systems. The Physical Layer provides for transparent
transmission of data between Data Link Layer entities across physical
connections.
The Physical Layer receives data from the Data Link Layer, adds preamble and
delimiters, provides encoding and transmits the resulting physical signals to the
wire medium. Signals are then received at one or more other devices and
decoded and stripped of preamble and delimiters before being passed to the
Data Link Layer of the receiving device(s).
Figure ?.?? shows a physical realization of a simple H1 network using Relcom
physical media. Please note that the RelCom FCS-PCT2 incorporates two (2)
terminators. The power supply may be any good 24 VDC supply that meets
the current requirements for the number of devices. Additional FCS-Es could
be added if more devices are added to the network.
Device Addressing
When installing instruments for the first time, it is recommended that each
instrument be installed one at a time and that you address the instruments in
succession (one after the other). Because like instruments have the same H1
foundation fieldbus address from the factory, you will only be able to see one
device. This condition will disable the installer from knowing which device he
is actually programming in the plant.
Also, the installer must decide which address to start with for each H1 node.
Currently, the linking device (address 10) addresses devices consecutively
starting at 18. Other Rockwell Interfaces, like the CN2FF (address 16), starts
numbering at 17. The FIM starts numbering at address 18.
Number of Devices per H1 Segment
The specified number of devices per H1 is 32. However, it should be noted
that most manufacturers would agree that the actual maximum limit to the
number of devices on the H1 is approximately 16. This is due to voltage drop
and the physical media that the system uses.
Rockwell Automation feels that the H1’s design is optimized by having 6 to 8
devices per H1 network. This optimized limit is mainly due to physical media,
the time required for each device to communicate, the extra bandwidth