Configuration Manual Owner manual

Publication 1757-PM002A-EN-E - June 2006
4-14 Applications
3. In the H1-1 Fieldbus window, right-click the linking device and select
Assign Tags.
A warning window appears.
4. Read the warning carefully and then select Yes.
The Assign Tag window opens and the Tag is sent to the Device. The
FI302 will momentarily disappear from the live list and reappear with
the new tag. Wait until the FI302 is solid in both the H1-1 live list before
proceeding.
5. Repeat steps 3-4 with the LD292.
New devices added to the H1 lines must be re-addressed. Doing this
optimizes network performance.
6. Use the H1-1 Live List to verify that the Device Tags have changed.
Add Function Blocks
1. In the H1-1 window, expand the linking device.
2. Right-click the FB VFD icon and click New Block.
The New Block window opens.