Configuration Manual Owner manual

Publication 1757-PM002A-EN-E - June 2006
4-16 Applications
Add Function Blocks to the Devices
Use the table below and the procedure from Add Function Blocksto add
additional Function Blocks to the devices.
Tag names should not have spaces in them for proper OPC communications..
Device Block Type Block Tag Parameter Element Value
FFLD Resource FFLD_Resource MODE_BLK TARGET Auto
ALERT_KEY 1
Logix FFLD_LGX MODE_BLK TARGET Auto
ALERT_KEY 1
SLOT (this value is used by
ControlLogix)
0
FI302 Resource FI302_RES MODE_BLK TARGET Auto
ALERT_KEY 1
Transducer FI302_TXD MODE_BLK TARGET Auto
ALERT_KEY 1
TERMINAL_NUMBER 1
Analog Output FI302_AO MODE_BLK TARGET CAS
ALERT_KEY 1
XD_SCALE (these values must
match the FINAL_VALUE_RANGE of
the transducer block
EU_100 20
EU_0 0
UNITS_DECIMAL mA
DECIMAL 2
CHANNEL (this must match the
TERMINAL_NUMBER of the
transducer block
1
LD292 Resource LD292_RES MODE_BLK TARGET Auto
ALERT_KEY 1
Transducer LD292_TXD MODE_BLK TARGET Auto
ALERT_KEY 1
Analog Input MODE_BLK TARGET Auto
ALERT_KEY 1
XD_SCALE (these values must
match the FINAL_VALUE_RANGE of
the transducer block
EU_100 5080
EU_0 0
UNITS_DECIMAL mm H20 (68°F)
DECIMAL 2
CHANNEL 1
L_TYPE Direct