4-36 Applications
6. Double-click the single ? on the Input Reference and select the
Controller Scoped tag, FFLD:0:I.In[1].SubStatus.
This function block will monitor the SubStatus of the AO
BKCAL_OUT for the Initialization Request.
7. Press <Enter>.
8. Click the FFLD:0:I.In[1].SubStatus pin, then the SourceA pin to connect
them.
9. From the Move/Logical tab, click the Band button and move the
Band block to the right of the Equal block.
10. Click the Output Reference button .
The Output Reference is added to your sheet.
11. Drag and drop the Output Reference above the Band block.
12. Double-click the single ? on the Output Reference and select the
Controller Scoped tag, FFLD:0:O.Out[0].Initializing.
This function block will send the Initializing Acknowledge status to the
AO CAS_IN based on the status of the PIDE and the Initialization
Request.
13. Press <Enter>.