Configuration Manual Owner manual

Publication 1757-PM002A-EN-E - June 2006
4-42 Applications
Replacing an Interchangeable Device
1. Physically connect the replacement device to the H1 network.
2. Right-click the failed device in H1 network and select Attributes.
3. In the Device Attributes window, use the drop-down selection for
Device Id to locate the new device.
4. Once the new device is selected, click OK.
5. Right-click the device again and select Download.
Replacing a Device of the same class
1. Physically connect the replacement device to the H1 network.
2. Create the replacement device in the RSFieldbus H1 network.
3. Right-click the replacement device in the H1 network and select
Attributes.
4. In the Device Attributes window, use the drop-down selection for
Device Id to locate the new device.
5. Once the new device is selected, click OK.
6. Create a Resource and Transducer block for the replacement device.
7. From the failed device, drag the function blocks in that device, with the
exception of the resource and transducer blocks, and drop them in the
replacement device.
8. Right-click the replacement device again and select Download.
9. Delete the failed device.