6-14 Additional Redundant Server Procedures
b. To add a directory, click Add, click , select the directory,
and click OK.
8. Click Save.
9. Click Yes to save the new connection.
10. Enter >defaultb.stn< in the File name field and click Save.
11. Select defaultb and click Connect.
12. Click Cancel at the Unable to connect prompt, if applicable.
13. Click Station Co n n ect to call up the Station Connect dialog
box.
14. Select Default and click Edit Connection.
15. On the Connection tab, make these entries to have the Station
point to SERVERA (PLX1 A):
a. In the Server field, enter or Br o w se to the Primary Server
name SERVERA.
b. Select the Station type as Static Station.
c. Enter >1< as the Static Station Number and click Advanced.
d. Check the Auxiliary setup file checkbox.
e. Click Br ow se and navigate to:
C:\Honeywell\Client\Station\defaultb.stn and click Op en .
16. Click Save.
17. Click Yes to save changes.
18. Select Default and click Connect.
19. Click Cancel at the Unable to connect prompt, if applicable.
TIP
Display Search Path Optimization
You can improve Station’s performance by
unchecking the Search subdirectories for shapes
checkbox in the Connection Properties dialog box,
and then explicitly defining each subdirectory that
contains displays.
IMPORTANT
You must indicate the full path to the .stn file.