Installation and Upgrade Guide
Publication 1757-IN510A-EN-P - October 2003
Firmware Maintenance Procedures 7-17
11. If you made no changes to dialog box values, click Can cel and
skip to
Step 17. Otherwise, continue with the next step.
12. Click OK to enter new values.
13. Click Yes in response to confirmation messages.
14. Wait for the data transfer to be completed. Click OK to
acknowledge the completion of the update without errors
prompt.
15. Click OK to acknowledge any communication prompt messages
that appear.
16. Click the pause button to halt the network scan.
17. If CNBs that reside on I/O networks are also to be updated, then
select one CNB from each I/O network for
Step 8 and repeat
Step 9 through Step 15 for each I/O network.
18. Click Network Tools ⇒ Ex i t to end the session.
19. Return to upgrade or installation procedures as applicable.
Updating Firmware in the 1757-ABRIO Module
Complete the following steps for updating the firmware in the
1757-ABRIO module.
1. Logon to the Server as ps_user.
2. Insert the ProcessLogix R510.0 Supplemental CD.
3. Click Start ⇒ Run .
4. Enter this path or Br o w se to:
>D:(or your CD-ROM drive letter)\ABRIO Control Flash\setup.exe<
5. Click OK.
6. At the Welcome to ControlFLASH Setup window, click Ne x t .
7. Click Yes to accept the License Agreement.
8. Click Ne x t to accept the default location.
9. Uncheck the Yes, I want to view the ControlFLASH readme file.